Mechanical installation
3.3 Mounting
The shock indicator shows if an acceleration has exceeded 98.1 m/s
the direction of acceleration. The black color of the arrows indicates that an impermissible
shock load has occurred in the direction of the arrow.
Danger to life caused by device damage when shock or tilt indicators have tripped
If a shock or tilt indicator has tripped, safe operation of the device cannot be guaranteed.
Death, serious injury, or material damage can result.
• Terminate the commissioning if one of the shock or tilt indicators has tripped.
• Contact Technical Support immediately for clarification.
Removing the shipping and handling monitors prior to commissioning
NOTICE
Material damage caused by transport indicators remaining in the device during operation
If transport indicators remain in the device during operation, material damage can result
from falling off or through temperature damage.
• Remove the transport indicators before commissioning the converter.
Ethyl alcohol can be used to remove any remains of adhesive after removing the transport
indicators from the control cabinet.
3.3.2.4

Unpacking

Unpacking
Check the delivery against the delivery note to ensure that all the items have been delivered.
Check that the cabinet is intact and has not been damaged.
The packaging material must be disposed of in accordance with the applicable country-
specific guidelines and rules.
3.3.2.5
Required tools
You require the following tools for installation:
● Standard set of tools with screwdrivers, screw wrenches, socket wrenches, etc.
● Torque wrenches 1.5 Nm to 100 Nm
● 600 mm extension for socket wrenches