Technical specifications
12.3 Technical data
Article number
Recommended protection
- Line protection
(with option L26)
Rated current
frame size to IEC 60269
- Line and semiconductor
protection
(without option L26)
Rated current
Frame size to IEC 60269
Short-circuit current rating per IEC
6)
Minimum short-circuit current
Rated output of a typical 6-pole standard induction motor based on I
1)
The base-load current I
2)
(see "Overload capability").
The base-load current I
3)
(see "Overload capability").
The current values given here are based on the rated output current.
4)
The recommendations for the North American market in AWG or MCM must be taken from the appropriate NEC
5)
(National Electrical Code) or CEC (Canadian Electrical Code) standards.
In conjunction with the specified fuses or circuit breakers.
6)
Minimum current required for reliably triggering protective devices.
7)
654
6SL3710-
2GH41-8EA3
Per sub-cabinet:
3NA3365-6
A
2 x 500
3
Per sub-cabinet:
3NE1435-2
A
2 x 560
3
kA
2 x 85
A
2 x 1800
7)
is based on a duty cycle of 110% for 60 s or 150% for 10 s with a duty cycle duration of 300 s
L
is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s
H
2GH42-0EA3
Per sub-cabinet:
3NA3362-6
3 x 425
3
Per sub-cabinet:
3NE1436-3
2 x 630
3
2 x 85
2 x 2000
or I
at 690 V 3 AC 50 Hz.
L
H
Operating Instructions, 07/2016, A5E03347396A
2GH42-2EA3
Per sub-cabinet:
3NA3365-6
3 x 500
3
Per sub-cabinet:
3NE1334-2
3 x 500
2
2 x 85
2 x 2300