Connection - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Electrical installation
4.10 Other connections
4.10.18.2

Connection

X520: Encoder connection 1 for HTL/TTL encoder with open-circuit monitoring
Table 4- 53
Connector type: 15-pin Sub-D socket
Measuring current via temperature sensor connection: 2 mA
Accuracy of the temperature measurement:
1)
- KTY: ±7 °C (including evaluation)
- PT1000: ±5 °C (PT1000 tolerance class B according to EN 60751 including evaluation)
- PTC: ±5 °C (including evaluation)
Danger to life due to electric shock in the event of voltage flashovers at the temperature
sensor
Voltage flashovers in the signal electronics can occur in motors without safe electrical
separation of the temperature sensors.
• Only use temperature sensors that fully comply with the specifications of the safety
160
Encoder connection X520
Pin
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
WARNING
isolation.
Signal name
+Temp
1)
Reserved, do not use
Reserved, do not use
P encoder 5 V/24 V
P encoder 5 V/24 V
P sense
M encoder (M)
-Temp
1)
M sense
R
R*
B*
B
A*
A
Technical data
Temperature sensor connection KTY84-
1C130 / PT1000 / PTC
Encoder supply
Encoder supply
Sense input encoder power supply
Ground for encoder power supply
Temperature sensor connection KTY84-
1C130 / PT1000 / PTC
Ground sense input
Reference signal R
Inverse reference signal R
Inverse incremental signal B
Incremental signal B
Inverse incremental signal A
Incremental signal A
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A