Parameter macro p1000 = 1: PROFIdrive (100001)
This macro is used to set the default setpoint source via PROFIdrive.
Table A- 6
Parameter macro p1000 = 1: PROFIdrive
Parameters
p1070
Main setpoint
p1071
Main setpoint scaling
p1075
Supplementary setpoint
p1076
Supplementary setpoint scaling
Parameter macro p1000 = 2: Terminal TM31 (100002)
This macro is used to set analog input 0 on customer terminal block TM31 as the setpoint
source.
Table A- 7
Parameter macro p1000 = 2: TM31 terminals
Parameter
p1070
Main setpoint
p1071
Main setpoint scaling
p1075
Supplementary setpoint
p1076
Supplementary setpoint scaling
Parameter macro p1000 = 3: Motorized potentiometer (100003)
This macro is used to set the motorized potentiometer as the setpoint source.
Table A- 8
Parameter macro p1000 = 3: Motorized potentiometer
Parameters
p1070
Main setpoint
p1071
Main setpoint scaling
p1075
Supplementary setpoint
p1076
Supplementary setpoint scaling
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
Sink
Description
Vector
Vector
Vector
Vector
Sink
Description
Vector
Vector
Vector
Vector
Sink
Description
Vector
Vector
Vector
Vector
DO
Parameters
r2050[1]
PROFIdrive PZD2
1
100 %
0
1
100 %
DO
Parameter
r4055
AI0 TM31
1
100 %
0
1
100 %
DO
Parameters
r1050
Motorized potentiometer
1
100 %
0
1
100 %
Appendix
A.2 Parameter macros
Source
Description
Vector
Vector
Vector
Vector
Source
Description
TM31
Vector
Vector
Vector
Source
Description
Vector
Vector
Vector
Vector
DO
DO
DO
669