The AA alarm has to be acknowledged within an acknowledge time
and the AA alarm has to be reset within an investigation time, else the
output(s) for routing equipment (fire brigade tx) will be activated.
During the acknowledge and investigation times:
If a fire alarm is activated by a detector / zone not programmed for
Alert Annunciation or if fire alarm is activated by a manual call
point, the output(s) for routing equipment (fire brigade tx) will be
activated.
If "Multiple alarms allowed within same zone" is set via EBLWin,
more than one AA alarm is allowed within that zone.
"Number of zones" can be set via EBLWin. Normally only one
zone with AA alarm is allowed but up to four zones can be
allowed.
Acknowledge and Reset is done on the Alert annunciation unit 1735 /
1736 or Alert annunciation controller 1740. A programmable output
("Alert Annunciation Activated") for indication and programmable
inputs ("Alert Annunciation Acknowledge" and "Alert Annunciation
Reset") can also be used. In some conventions can this also be done
in the c.i.e. (with the dark grey button with no text).
The Acknowledge time can be set to 0-120 seconds.
The Investigation time can be set to 0-9 minutes.
NOTE! According to EN54-2, the total delay of fire alarm routing
equipment must not exceed 10 minutes (i.e. Acknowledge time +
Investigation time < 10 min.).

Alarm Acknowledgement Facility (AAF)

This facility is used on the Australian market only.
One AAF zone can consist of one to five analog smoke detectors
(4300 / 4301 / 4400 / 4401 ), one AAF buzzer (e.g. Sounder base
3379) and one AAF Control (AAFC)
loop.
107
This unit is available on the Australian market only.
104
EBL128 Planning Instructions V2.0.x
107
. All connected on one COM