Interlocking function

The interlocking function is used to verify that an output really is
activated, i.e. by "combining" an output with an input (feed-back from
the equipment controlled by the corresponding interlocking output).
Input
EBL128
Output

Interlocking programming

EBLWin is used for the programming.
Combinations can be used.
NOTE! Each interlocking input and each interlocking output can
only be used in one interlocking combination.

Interlocking output

The "Voltage Output" / "Relay Output" dialog boxes are to be used.
Type: "Interlocking" is to be selected.
Output signal period:
activation is to be selected.
Control Expression is to be programmed for the output, i.e. for the
equipment to be controlled.
Activated output will be indicated in menu H9/C1.
Name: It is recommended to add information, e.g. the interlocking
combination's presentation number (Area-Point).

Interlocking input

The "Input" dialog box is to be used.
Triggered by: "Interlocking Input" is to be selected.
Activated input will be indicated in menu H9/C1.
Name: It is recommended to add information, e.g. the interlocking
combination's presentation number (Area-Point).

Interlocking combination

One interlocking output plus one interlocking input are programmed
in one interlocking combination to get the interlocking functions.
NOTE!
The interlocking outputs and inputs have to be programmed before the
programming of an interlocking combination is possible to do.
An interlocking combination can have only an output or only an input
programmed, e.g. if a text shall indicate an activated output or input.
89
In the "Interlocking Combination" dialog box are listed all the outputs and
inputs previously programmed for interlocking, see Figure 16.
EBL128 Planning Instructions V2.0.x
Feed-back signal
Up to 100 Interlocking
Steady (continuous) or Steady, delayed
86
Controlled
equipment
89