Panasonic EBL128 Planning Instructions page 80

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
10.5.1.4
Other
35
Indication Fire Brigade Tx Activated
36
Indication Fault Tx Activated
37
General Fault
38
General Mains Fault
39
Reset Pulse Zone Address (+Zone no. +Address)
40
Time Channel Activated (+Time channel name / no.)
41
Alert Annunciation Activated
42
Alert Annunciation Acknowledged
43
Door Open
44
Fire Door Closing (+Zone no. +Address)
45
General Service Signal
46
Fire brigade Tx
47
Door Open Control Unit (+Control unit)
48
Extinguishing System Fault
49
Extinguishing System Released
50
Activated Key Cabinet
51
Fault Control Unit (+Control unit)
52
Consecutive Fault Control Unit (+start Control unit and
stop Control unit)
53
Zone Fault (+Zone no.)
54
External Fault (+ext. fault)
55
Technical Warning (+techn. warning)
56
General Technical Warning
Comments to the trigger conditions (functions):
Alarm
1
Fire alarm. For more information regarding fire alarm,
see EBL128 Operating Instructions MEW01623. Output
is activated when the specified Zone is in alarm.
2
See 1. Output is activated when the specified alarm point
is in alarm.
3
See 1. Output is activated when any alarm point or Zone
is in alarm.
4
See 1. Quantity (1-10): "1" means one unit in alarm is
required, "2" means two units in alarm are required to
activate the output and so on.
5
Pre-warning.
warning,
MEW01623.
Zone is over the pre-warning level.
75
Not valid for the 3364 outputs (VO0-VO2).
76
The trigger condition is true as long as the pre-warning level is exceeded.
It is also true as long as the fire alarm level is exceeded even if the option
pre-warning detection is disabled (via EBLWin).
EBL128 Planning Instructions V2.0.x
76
For more information regarding pre-
see
EBL128
Operating
Output is activated when the specified
78
75
Instructions