Panasonic EBL128 Planning Instructions page 45

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
6.1.1.6
Accessories
3314 Address setting tool. Replaced with 4414, see below. Is used
to write or read the COM loop units' technical address (001-
255). It is also used to write or read the mode, NORMAL or
2330 (see the unit respectively). A connection cable (with
crocodile clips and tab terminals) is attached and can be used
when required.
Put the ON/OFF switch in position ON and wait for a beep.
Plug the detector into 3314 (SA & SB terminals) or when
required, use the connection cable.
How to read: Press "READ", wait for a beep and read the
address and mode.
How to write: Press "WRITE" and "READ" at the same time to
select the mode and/or write the address. Press "WRITE" and
wait for a beep. ("READ" again as a check.)
4414 Address setting tool. Replaces 3314. Is used to write or read
the units' COM loop address (Technical address 001-255). It
is also used to write or read the mode (Advanced
2330 and 2312), see the COM loop unit respectively for mode
information.
A connection cable with crocodile clips and tab terminals is
supplied with the tool and can be used when required.
4414 (orange front) will replace 3314 (grey front) but 4414 is
only required when the 4400 and 4401 detectors shall be used in
Advanced mode.
Turn on the tool (On/Off/CLR button). A blinking curser and
mode M0 will be shown in the display. Plug the detector's SA
& SB terminals onto the tool's SA & SB terminals or, when
required, use the connection cable.
How to read: Press "Read", wait for the OK, address and mode
info. and a beep.
How to write: To change the mode (if required) press "Write"
and "Read" at the same time, then press 0, 1, 2 or 3 for the
mode respectively. Type the address (no beginning zeroes) and
press "Write". Wait for the OK, address and mode info. and a
beep. (Press "Read" again for a double check.) More info. on
the backside of the tool.
44
Some units have flying leads for easier connection. After use they might
be disconnected and thrown away.
45
Address setting tool 4414 has to be used to set the detectors 4400 and
4401 in Advanced mode. (Address setting tool 3314 cannot be used for the
Advanced mode.)
46
Some units have flying leads for easier connection. After use they should
be disconnected and thrown away.
EBL128 Planning Instructions V2.0.x
44
46
43
45
, NORMAL,

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents