Panasonic EBL128 Planning Instructions page 151

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
Validate...: The SSD can at any time be validated, i.e. checked for
System Errors, Warnings and EN54 violations. A validation will
automatically be done before download of SSD to EBL128. System
Errors have to be corrected before the download can start.
Log on control unit: Log on / Log off to an EBL128.
Synchronize...: (When connected and logged on to an EBL128.)
Data (i.e. faults, disablements, etc.) will be synchronized, i.e. the data
/ information are the same in the control unit and EBLWin.
Download SSD...: (When connected and logged on to an EBL128.)
Opens a dialog box for download of SSD to the EBL128 control unit,
the Web-server and connected "Display Units" (e.g. Ext. FBP).
Backup SSD ("Upload")...: (When connected and logged on to an
EBL128.) Opens a dialog box for backup ("upload") of SSD from
EBL128 and connected "Display Units" to EBLWin.
Verify SSD...: (When connected and logged on to an EBL128.) The
SSD shown in EBLWin will be compared with what is actually stored
in EBL128. Same checksums = same SSD.
Erase SSD...: (With EBL128 in boot mode.) The SSD stored in the
EBL128 control unit will be erased. Also the SSW (see Operating
Instructions) will be erased. NOTE! An EBLWin key is required.
Reset user passwords...: (When connected and logged on to an
EBL128.) If any password is changed via the control unit menu (H10)
or via a Web-server, it will be reset to the password downloaded via
the SSD, i.e. the passwords in the EBLWin dialog box "User data"
(found in the menu "System").
Download Software...: (When connected and not logged on to an
EBL128.) NOTE! An EBLWin key 5094 is required. Opens a
dialog box for download of an EBL128 S/W file (xxx.bin) to an
EBL128 control unit. (There is one .bin file for each language /
customer.)
Download FBP/EPU/AAU software: (When connected to a Display
Unit – via RS232.) For download of S/W (xxx.bin file) to one
Display unit. NOTE! An EBLWin key 5094 is required.
Options...: EBLWin settings. A Convention (one for each country)
is selected the very first time EBLWin is opened. Can be changed if
Level 2 is selected, see below. Display Unit language can be selected
as well as the EBLWin language.
Advanced Functions:
No "Level" selected (default) = Alarm algorithm parameters cannot be
changed.
"Level 1" selected = Alarm algorithm parameters, except the fire
alarm parameters can be changed.
"Level 2" selected (a password is required) = Also the fire alarm
133
Log on require the PC to be physically connected to EBL128 and an
EBLWin key 5094 plugged in the PC.
149
EBL128 Planning Instructions V2.0.x
133