Input Programming; Type (Trigger Conditions) - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
8
8.1

Input programming

Input programming is done via EBLWin. Each input has to have an
individual Trigger condition ("Type") and Logic. Each input can be
supervised or not supervised.

Type (trigger conditions)

The following trigger conditions are available (numbers only for the
paragraph "Comments to the trigger conditions"):
1. Activate output
2. Activated fault routing equipment (one input)
3. Activated fire ventilation (one input)
4. Activated key cabinet (one input)
5. Activated Routing Equipment (one input)
6. Alarm Key Cabinet (one input)
7. Alert Annunciation Acknowledge
8. Alert Annunciation Reset
9. Door Closing Test Input
10. Evacuate (one input)
11. External Fault (up to 50)
12. External Time Channel (one input per time channel)
13. Extinguishing alarm
14. Extinguishing start
15. Extinguishing stop
16. Extinguishing system fault (one input)
17. Extinguishing system released (one input)
18. Fault Signal External Fuses (one input)
19. Fault Signal External Power Supply (one input)
20. Fault warning routing equipment fault (one input)
21. General Fire (max. 100)
22. Interlocking (max. 100)
23. Loss of battery charger to external power supply (one input)
24. Loss of main power source to external power supply (one
input)
25. Not used
26. NZ Silence switch (one input)
27. Pre-warning
28. Technical warning (up to 50)
64
29. Zone Line Input
Comments to the trigger conditions:
64
Only valid for the Addressable multipurpose I/O unit 3361 input "In0",
used as zone line input (Z).
EBL128 Planning Instructions V2.0.x
64