Panasonic EBL128 Planning Instructions page 83

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
36
The control expression is true (output activated) when
LED "Fault tx activated" is lit, i.e. when the routing
equipment output (Fault tx) is activated.
37
Output activated when one or more faults are generated
in the system.
38
Output activated for loss of mains (in the c.i.e. or external
power supply 3366). NOTE! The output(s) will be
activated immediately but the corresponding fault is
normally delayed (set via EBLWin).
39
The control expression is true (output activated) for 5
seconds, whenever a reset pulse is sent to the specified
Zone-Address.
40
Output activated when the specified time channel is
activated.
41
Output activated when Alert annunciation alarm is
activated (by any alarm point set to activate this
84
function).
Operating Instructions MEW01623.
42
Output activated when Alert annunciation alarm is
activated (by any alarm point set to activate this
84
function)
see EBL128 Operating Instructions MEW01623.
43
Output activated for Door open in the control unit or in
any Ext. Fire Brigade Panel in the system.
44
This trigger condition plus the OR operator shall be used
for each detector (Zone-Address) controlling a fire door
(normally > two detectors). Type of output is normally
"Control, neutral".
Door Closing function", page 92.
45
Output activated when Service signal is activated (by any
87
sensor).
46
The control expression is true (output activated) when the
control unit standard output "Fire brigade tx" is activated.
NOTE!
equipment (Fire brigade tx).
47
Output activated for Door open in the control unit.
82
Which is indicated by LED Routing equipment "Fault tx activated". This
output will also be activated when the routing equipment test is performed
via menu H1.
83
Which is indicated by LED Fault / Disablements "General fault" and/or
LED Routing equipment "Fault tx activated".
84
Valid until the AA alarm is reset or becomes a normal fire alarm.
85
Which is indicated by the LED "Door open" in the c.i.e.
86
In Danish convention (DBI), must only the c.i.e. outputs R0 and S0-S1 be
used (or COM loop unit 3364) and the type has to be "control neutral".
87
Indicated by the LED "Service" in the c.i.e.
EBL128 Planning Instructions V2.0.x
83
For more information, see EBL128
and acknowledged. For more information,
86
Output activated, see chapter "Fire
Normally used with output type Routing
81
82
85
85