24.5
NOTE! The values are calculated and give only a rough idea of the
back-up time.

Form / Table of current consumption

Some national regulations require different forms / tables regarding
current consumption, to be filled in. In such a case an ampere meter
shall be used instead of calculating the current consumption.
A tip: Disconnect the mains and use a "clamp current meter" to read
the current consumption from the battery, i.e. the total control unit
consumption.