In EBL128 can totally up to 200 outputs be used, including all kinds
of outputs.
For more information (e.g. application board type selected via jumpers
JP4-JP5), see the I/O Matrix board 4582, Technical description
MEW00914.
Each I/O Matrix board has to be programmed via EBLWin
regarding:
Address, set via jumpers "JP1-JP3", see Figure 5, page 25.
Type of board (Generic / Fan control / Zone control)
LED test on Input 15 or no LED test on Input 15
The 4582 board has 48 LED outputs and 16 switch inputs (0-15).
Depending on if the Application board is of the type Generic, Fan or
Zone, the outputs and inputs are programmed differently.

Generic

Used for application board type Generic.
Each output (0-47) has to be added and programmed via EBLWin
regarding:
Output no. (0-47)
Properties like for any programmable relay output.
Each input (0-15) has to be added and programmed via EBLWin
regarding:
Input no. (0-15)
Type (of input)
Properties (e.g. zone-address, alarm text) like for any
programmable input.

Fan control

Used for Application board type Fan control, e.g. "Fan control
application board" 4594, which has a front for control of four fans.
EBL128 Planning Instructions V2.0.x
30