Download SSD

The PC program EBLWin is used for creating the Site Specific Data
(SSD) and to download it to the EBL128 control unit, the Web-server
and/or connected Display Units 1728, 1735, 1736, 1826 & 1828.
When the installation is ready, i.e. all units connected and the power is
turned on, the SSD download can take place.
The PC has to be connected to the RS232 port "J3" in the control unit.
Start EBLWin and open the wanted installation. Log on to the control
unit via the PC (EBLWin).
NOTE!
No password / access code is required to log on to the control unit,
instead an EBLWin key (5094) is required. This key is plugged in a
USB-port in your PC.
In EBLWin (menu "Tools" | "Download SSD...") select the Control
unit "0".
SSD can also be downloaded to the Web-server and
connected Display Units if the checkbox "Download display units"
and "Download Webserver SSD" respectively, is marked.
After the SSD download the control unit will restart. A number of
faults might then be generated, e.g. due to not connected units.
Disconnected at startup
Normally this function is not used in EBL128 since this control unit
has only one COM loop.
In the COM loop Properties dialog box it is possible to select the
option "Disconnected at startup".
disabled directly after the download restart and therefore not generate
any faults.
NOTE!
A COM loop "Disconnected at startup" can be re-connected via menu
H8/S1 but it will then be disconnected again after next SSD download.
Finally the SSD for that control unit has to be downloaded again with
the option " Disconnected at startup" not selected.

COM loop menu

Check Loop

NOTE! If any "Obsolete units" are connected the result of this check
might be incorrect.
In the EBLWin COM loop icon pop-up menu select "Check Loop".
This function can be used after (or before) the download of SSD. The
function is as follows:
The control unit will find connected expansion boards and all units
connected on the COM loop. If there is a break (cut-off) or short
circuit on the loop only the units in the A-direction will be found and
151
EBL128 Planning Instructions V2.0.x
The COM loop will then be

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents