Panasonic EBL128 Planning Instructions page 81

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
6
See 5. Output is activated when the specified alarm point
is over the pre-warning level.
7
See 5. Output is activated when any alarm point or Zone
is over the pre-warning level.
8
See 5. See also 4 above regarding "Quantity".
9
Heavy smoke / heat alarm.
regarding heavy smoke / heat alarm, see EBL128
Operating Instructions MEW01623. Output is activated
when the specified Zone is over the heavy smoke / heat
level.
10
See 9. Output is activated when the specified alarm point
is over the heavy smoke / heat level.
11
See 9. Output is activated when any alarm point is over
the heavy smoke / heat level.
12
See 9. See also 4 above regarding "Quantity".
13
Output is activated when only one address (in two-
address dependence) is in fire alarm state. For more
information,
MEW01623.
14
Output is activated when only one zone (in two-zone
dependence) is in fire alarm state. For more information,
see EBL128 Operating Instructions MEW01623.
15
Output activated when "Multiple detector alarm" is true,
i.e. fire alarm type A.
16
Output activated when "One detector alarm" is true, i.e.
fire alarm type B
17
General Key cabinet alarm activated.
information,
MEW01623.
18
Alarm Acknowledgement Facility.
(require special hardware). "Alarm" is activated in the
specified AAF zone.
19
Output activated for any "Quiet alarm" in the specified
zone. Used e.g. for the fan control function.
20
Output activated for one specified "Quiet alarm" in the
specified zone-address. Used e.g. for the fan control
function.
21
This control expression is true (i.e. output activated) for
15 seconds after the last alarm is reset.
Interlocking
22
Output activated when one or more interlocking inputs, in
the specified interlocking area, are activated.
23
Output activated when the interlocking input, in the
specified interlocking area/point, is activated.
24
Output activated when any interlocking input is activated.
77
See chapter "Fire alarm type A and Fire alarm type B", page 106.
EBL128 Planning Instructions V2.0.x