Disconnect / Re-connect COM loop

The COM loop can be disconnected via menu H8/S1. Disconnected
COM loop will stay disconnected until Re-connect via menu H8/S1.

Disconnect / Re-connect zone line input

A zone line input (e.g. on a 4580 board) can be disconnected via menu
H8/S2. Disconnected zone line input will stay disconnected until Re-
connect via menu H8/S2.
Disconnect / Re-connect addressable zone interface
input
A zone interface input (e.g. 2226/2335/2821/3361) can be
disconnected via menu H8/S3. Disconnected zone interface input will
stay disconnected until Re-connected via menu H8/S3.

Disable interlocking output

The control outputs of type "Interlocking output" can be disabled via
menu H9/C4. Disabled outputs will stay in (or return to) the normal
condition for the output respectively until Re-enable via menu H9/C5.

Test mode

Alarm points / zones can be tested during the Monthly test (via menu
H1) or via menu H7. Up to 99 zones can be set in Test mode via
menu H7 but only four zones via menu H1. For more information see
the EBL128 Operating Instructions. The LED "Test mode" indicates
one or more zones in Test mode. Zones in Test mode are also
simultaneously shown in the EBL128 display.
the testing time, any time delay for the detectors / zones in test mode
will be "shortened", i.e. fire alarm will be activated faster than
normally.

Test alarm devices

The programmable outputs type "Alarm device" can be collectively
activated via menu H8/S6, which make it possible to test the alarm
devices.
(The test cannot be started if a fire alarm already is
activated.) When the test starts the alarm devices will be turned "ON"
for 1 second (±1s), "off" for 29 seconds (±1s), "on" for 1 second and
111
so on.
NOTE! Also disabled (and silenced) alarm devices will be tested.
The test will continue for one hour if it is not stopped via menu H8/S6
or if a fire alarm is activated in the system.
110
Disablements, faults and fire alarms have higher priority, i.e. the
presentation of zones in Test mode will be suppressed during such a
condition.
111
The output activation will be continuously (steady).
devices 3377/4477 and 3378/3379, the tone with the highest priority level
(and type "alarm device") will be automatically selected.
110
EBL128 Planning Instructions V2.0.x