Panasonic EBL128 Planning Instructions page 137

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
17.1.4.1
17.1.4.2
Enhanced disablements: Disabled alarm point will not activate
pre-warning, fire alarm or fault.
Checkbox not marked = Disabled alarm point will not activate
pre-warning or fire alarm. Fault can still be activated.
This is a violation to the EN54-2 standard.
Use special menu during fire alarm: Function, see Operating
Instructions (MEW01623) chapter "Fire alarm menu (X1-X9)".
Door closing by time
Active: If all fire doors (trigger condition "Fire Door Closing")
shall be closed at a definite time every day, this checkbox shall be
marked and the time (hh:mm) set, e.g. 23:00.
Main power loss fault delay time (minutes)
A fault will be activated mm minutes after loss of mains (230 V AC).
30 is default. 0-300 minutes is possible. >30 min. is an EN54-2
violation.
135
EBL128 Planning Instructions V2.0.x