6.3
6.3.1
FBF 2003 German
Fire
Bedienfeld). A grey metal housing (HxWxD, 185 x 255 x 58
mm) with a door. A key is required to open the door, which has
a Plexiglas ahead of the front. It has cable inlets on the top,
bottom and back sides and is intended to be wall mounted.
The function, LED indicators and push buttons on the front are
in accordance with DIN 14661. The front's designation texts
are in German. Serial RS485 interface for IHD protocol.
The unit is power supplied from EBL128 (or an ext. power
supply). Up to 1200 m cable can be used.
NOTE! Switch 1 on the DIP switch shall be set to "on".
FAT 2002 German Fire Brigade Indicator Panel (Feuerwehr-
Anzeigetableau). A grey metal housing (HxWxD, 185 x 255 x
58 mm) with a door. A key is required to open the door, which
has a Plexiglas ahead of the front. It has cable inlets on the top,
bottom and back sides and is intended to be wall mounted.
The function, Display information, LED indicators and push
buttons on the front are in accordance with DIN 14662. The
front's designation texts are in German.
interface for IHD protocol.
The unit is power supplied from EBL128 (or an ext. power
supply). Up to 1200 m cable can be used.

Units connected to the RS232 interface J5

Web-servers

1598
Web-server II. This unit can be used:
a) for presentation of the actual c.i.e. status in a PC using the
web browser Microsoft Internet Explorer. It can also send e-
mails in case of pre-warning, fire alarm, fault, disablement,
test mode alarm and/or service signal.
b) for remote control via two-way communication. Up to 10
User names with an individual Password and three different
access types / levels.
c) as a gateway to other PC systems etc.:
c1) EBL Talk is an open protocol, used to transmit and
present fire alarm information in a separate PC / system.
(RS232 or TCP/IP)
c2) Tateco, used to transmit and present fire alarm
information in an Ascom Tateco paging system. (RS232)
c3) SIA, used to transmit and present fire alarm
information in a separate PC application. (RS232)
d) EBLnet. (TCP/IP) EBLnet Software Development Kit is
used to develop your own Security Management System.
The tool for the Web-server configuration is a part of the PC
program EBLWin.
downloaded to the web-server via TCP/IP.
EBL128 Planning Instructions V2.0.x
Brigade
Control
The Web-server configuration is
57
Panel
(Feuerwehr-
Serial RS485

Hide quick links: