Addressable I/O Units - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
6.1.2
3390 Label holder.
To be mounted on the analog base 3312
Intended for a label with "zone-address", "technical address",
etc. to be read also when the detector is plugged in its base. 100
label holders per packet. Excl. labels.
3391 Labels for 3390. Packet with self-adhesive white labels for
label holder 3390. 10 A4-sheets à 132 labels for laser printer
usage. The print-out is done via EBLWin.

Addressable I/O units

3361 Addressable multipurpose I/O unit.
COM loop.
The unit has two programmable inputs:
Monitored input
....used as zone line input (Z): End-of-line capacitor 470 nF
mounted in the last unit on the line. A short circuit can activate
fault or fire alarm (set via EBLWin). This input is intended for
conventional detectors.
....used as general input (In0): An input for NC or NO
contacts (set via EBLWin).
Isolated input (In1): An optocoupler input (external 24 V DC
/ 8 mA is required). Normally low or high (set via EBLWin).
The unit has two programmable relay
Relay output (Re0): NC or NO contacts (set via EBLWin).
Relay output (Re1): NC or NO contacts (set via EBLWin).
Connections and examples, see drawings 128-21 & -26. The
unit's dimensions: (L x W x H) 90 x 70 x 32 mm. A plastic
protection cover is attached. The cover's dimensions: (L x W x
H) 129 x 73 x 45 mm. The unit is intended to be surface
mounted and for indoor use in dry premises. When required,
the unit can be mounted in a Waterproof box (IP66 / 67) 3362.
The unit has an LED to indicate communication to the unit or
alarm condition. For more information, see the Product Leaflet.
The technical address is set with an Address setting tool 3314 /
4414. The unit has an address label on which the programmed
technical address is to be written.
The Address setting tool is also used for mode setting:
47
Also in the enclosed analog heat detector 3309.
48
The same physical unit (3361) is also used for the Australian Fan control
function and has a separate dialog box in EBLWin.
49
It is via EBLWin possible to define this input functioning like a manual
call point ("Used as MCP"), i.e. it will not be collectively disabled via menu
"Disable zone, H2/B1", can not be included in two-unit dependence, it can
not use the "alarm delay" function and it can not be disabled via a time
channel.
50
Relay contacts: max. 2 A @ 30 V DC / 125 V AC.
EBL128 Planning Instructions V2.0.x