9.1
Each 3377, 4477, 3378 and 3379 unit is programmed (EBLWin)
regarding:
Technical address
Name (Normally not changed)
Priority level (High / Medium / Low)
For each priority level:
 Sound type (different for each priority level)
 Name
 Type (Normally "Alarm device")
 Output signal period (Normally "Steady")
 Control expression (with one or more trigger conditions)
If Enter arguments in dialog is selected a separate dialog box
is opened for easier entering of the required data (e.g. zone,
address, etc.).
expression is. It must be < 80.
Figure 12. The EBLWin dialog box "Addressable siren 3377"
(The dialog box for 3378 / 3379 is similar). For "Addressable
siren with isolator 4477" also a Sequence number.
Control unit outputs S0 – S1
EBL128 has two programmable, supervised (monitored)
outputs:
S0
Supervised (monitored) voltage output, 24V DC
mA (Fuse F8).
66
Supervised as default but via EBLWin it is possible to set each output
individually as not supervised (not monitored). A normally high output can
not be supervised.
Supervised outputs have to be calibrated via menu H5/A1, see the EBL128
Operating Instructions. 1-5 supervision resistors 33K can be used. The
calibrated value has to be in the range 4K7-50K. A fault will be generated
for a value outside this range. A normally high output will be low for a few
seconds during restart of EBL128.
67
See chapter "Technical data", page 143, regarding system voltage.
EBL128 Planning Instructions V2.0.x
SSD size indicates how big the control
69
66
voltage
67
, max. 500