12.1
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
Each 3377 and 3379 unit is programmed (WinG3) regarding:
COM loop address
Name (Normally not changed)
Priority level (High / Medium / Low)
 Sound
type
(Steady/continuous,
Alternating/two-tone)
 Output type (Normally "Alarm device")
 Output signal period (Activation - Steady/continuous, Steady
delayed activation or Steady delayed de-activation)
 Control expression
Figure 12. WinG3 "Addressable siren 3377" dialog box.
Control unit outputs S0 – S3
Each control unit has four programmable, supervised (monitored)
voltage outputs:
S0
Supervised (monitored) voltage output, 24V DC
S1
Supervised (monitored) voltage output, 24V DC
S2
Supervised (monitored) voltage output, 24V DC
56
S3
Supervised (monitored) voltage output, 24V DC
Connections and more information, see dwg. 512 G3 - 23.
55
This is default, but via WinG3 it is possible to set each output individually
as not supervised (not monitored). A normally high output is not supervised.
See also chapter "Calibration of supervised outputs", page 108.
56
Note! This output will be low in case of system fault (via the watch dog
reset circuit). May be used as a supervised voltage output for fault warning
routing equipment (Fault tx).
Intermittent/pulsed
69
or
55