Panasonic MEW01 351 Planning Manual page 134

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01351
Rev: -
20.1.3.2
20.1.3.3
20.1.3.4
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
Alarm Acknowledgement Facility
Used in conjunction with the AAF Control that is available on the
Australian market only.
See also chapter "Alarm Acknowledgement Facility (AAF)", page
104.
Investigation period (IP) time: 3 min.
3 is default. 1-3 is possible.
Acknowledge period (AP) time: 60 sec.
60 is default. 10-60 is possible.
Disable routing equipment by door switch
Valid for the following control unit outputs for routing equipment:
Fire alarm (for Fire brigade tx)
Fault condition (for Fault tx)
 None (default): Door open in a C.U. or an ext. FBP will not
disable these outputs.
 Any control unit door: Door open in any C.U. will disable these
outputs in all C.U:s.
 Any door: Door open in any C.U. or any ext. FBP will disable
these outputs in all C.U:s.
In the display (or via menu H4/U1) is shown (xx = C.U. number):
Fire alarm routing disabled
CU xx)
Alarm reset method
One of the following alternatives shall be selected.
 All (default):
All fire alarms in the system will be reset
simultaneously by pressing the "Reset" button (on the c.i.e. front)
once.
 Single: One fire alarm in the system, i.e. the fire alarm shown in
the field in the middle of the control unit display will be reset by
pressing the "Reset" button once. Any other fire alarm has to be
reset the same way, one by one.
This function is a violation to the EN54-2 standard.
 Single With Automatic Disablement: Like "Single" reset but
with the Disablement function (see below) as well.
This function is a violation to the EN54-2 standard.
Disablement function: If an alarm point or zone is reset while it still is
in alarm state (e.g. smoke in a smoke detector or a manual call point
with a broken glass) this unit will be automatically disabled in order to
not activate a new fire alarm within 20 seconds. It will stay disabled
until re-enabled via menu H2/B5.
LED Fault / Disablements "General disablements" on the c.i.e. front
is indicating one or more disablement in the system.
132