Planning Instructions Fire alarm system EBL512 G3, V1.1.x
disable, re-enable and activate programmable control outputs
set alternative alarm algorithm for analog detector types 430x
on / off
set 2-unit dependence function on / off
The properties for each Time channel (2-14) and each Day of the
week (Monday – Sunday + National Holiday) have to be set for the
channels that shall be used.
Figure 27. Left: The "Time channel 2" dialog box without any
programming done. Right: One time interval is programmed
for the Monday (time channel 2 is "on" 07:00 – 16:00).
Name: "Time channel n" is default. Normally not changed but an
informative text can be added (e.g. office hours).
Monday: Place the cursor (the "arrow") in the white day field (e.g.
Monday). In the "Cursor Time" area (down to the right) is the actual
cursor time displayed. Move the cursor in the day field. In the
"Cursor Time" area will the corresponding time be displayed. In the
correct time position (e.g. 07:00) click the left mouse button and drag
the cursor to the right (or left) to the next time position (e.g. 16:00)
and drop the cursor. There will now be a box in the day field
indicating the time interval when the time channel is "on". The time
interval (e.g. 07:00 – 16:00) is also displayed in the "Current Day"
area (down to the left).
For each day, two time intervals can be programmed. A time interval
can be edited by dragging the whole interval (or the left / right side of
it) to the left or right in the day field. Alternatively, double click the
time interval box in the day field to open a dialog box for easier time
editing:
135