Planning Instructions Fire alarm system EBL512 G3, V1.1.x
Clean condition, level 1, 2 & 3
For this learning condition to be adapted there must be no check-mark
for level 1, level 2 and level 3 respectively during the learning
period, i.e. no check-mark what so ever.
The Clean condition will be ended directly if any 36h period for
level 1, level 2 and level 3 respectively gets a check-mark, i.e. any
check-mark what so ever.
Learning condition summary
A detector can adapt the following learning conditions, depending on
if and when level 1, level 2 and level 3 are exceeded or not:
Normal condition (default)
or
Clean condition
or
Steam / tobacco condition and/or Heating condition and/or Cooking
condition
The following is valid for the different type of detectors:
4352: This detector uses not the Learning function.
4350: This detector uses the Learning function (for different alarm
threshold levels and alarm delay times, depending on smoke & temp.).
4301: This detector uses not the Learning function.
4300: This detector uses not the Learning function.

Alarm delay time

Depending on the detector type, mode and learning condition the
delay times before fire alarm threshold level was exceeded, are for the
different type of detectors:
4352: Normally 9 seconds.
4350:
#3
NOTE! Max. alarm delay time is 60 seconds.