Planning Instructions Fire alarm system EBL512 G3, V1.1.x
Comments to the trigger conditions (above):
0. Activates any output as long as the input is active. This is valid
even if the output is disabled.
1. "Activated Fault routing equipment" signal (feed-back) to
EBL512 G3 will light up the LED "Fault tx activated" on the
front.
Output with trigger condition "Indication Fault tx
Activated" will be activated.
2. Output with trigger condition "Activated Key cabinet" will be
activated.
3. Activated Fire brigade tx feedback to the EBL512 G3 control unit
to light up the LED "Fire brigade tx".
4. Key cabinet, where the fire brigade store there key to the building.
Will activate a Key cabinet alarm. See EBL512 G3 Operating
Instructions for more information.
5. Alert annunciation, see chapter "Alert Annunciation", page 102
and EBL512 G3 Operating Instructions for more information.
6. Like 2.
7. When one or more "Fire door closing" outputs are used, these
outputs will be activated for 20 seconds by this trigger condition.
NOTE! Only valid for inputs and outputs connected to the same
c.i.e.
8. Normally used for the New Zealand key switch "Evacuation".
The function is like the soft key "Evacuate" (P7) on the c.i.e.
53
front.
The input has to be activated as long as the Evacuate
function shall be on.
9. Ext. fault will activate a fault in EBL512 G3. A user definable
fault message ("Error text") up to 40 characters will be shown.
10. External clock, timer, key switch, etc. can disable / re-enable
alarm points. The function Alert Annunciation, etc. can be turned
on / off by a time channel. Control outputs can be turned on / off
by a time channel.
11. Input activated when the specified zone has activated fire alarm.
The specified zone is an "extinguishing zone", e.g. a sprinkler
zone. This trigger condition is normally used only for the "New
Zealand indicating panel" in order to control the function of the
key switch "Silence alarms".
51
One input activated in any control unit, will light up the LED respectively
in all control units.
52
One input activated in any control unit, will light up the LED respectively
in all control units.
54
In the WinG3 dialog box "Input".
51
52
65