External Fire Brigade Panels - Panasonic MEW01 351 Planning Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01351
Rev: -
9.2.1
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
Via WinG3 can "Selective alarm presentation" be programmed, i.e.
you can select which alarms that shall be presented in each unit, see
the Technical Description for the unit respectively.
NOTE! As an alternative, German Fire Brigade Panels (see page 58)
can be connected to the RS485 interface.

External Fire Brigade Panels

1826 External Fire Brigade Panel (ext. FBP). A light grey metal
housing (HxWxD, 288 x 400 x 95 mm) with a door. A key is
required to open the door, which has a Plexiglas ahead of the
FBP front. It has cable inlets on the top, bottom and back sides
and is intended to be wall mounted. Two compression glands
are attached.
LED indicators and push buttons on the front are like the
EBL128 FBP (upper black part of the front), see Figure 2, page
20. The front's designation texts are in Swedish. A neutral
front is available, where the designation texts, in any
language, are made separately and by production put into a
transparent "text slot" for the LED and push button respectively.
All or selected alarms will be presented in a display
(alphanumeric LCD, 2x40 characters), with back-light.
alarm text will also be presented together with each alarm, if
programmed in EBL512 G3. Furthermore, at least 617 texts for
selected fire alarms can be stored in the unit and will in such a
case be shown, instead of the texts sent from EBL512 G3 for
these alarms. These text messages will be downloaded to the
unit via EBL512 G3. A built-in buzzer will sound like in
EBL512 G3. The buzzer can be silenced and the alarm devices
in the installation can be silenced. They will re-sound for a new
alarm. When there are queued alarms in the system, you can
scroll amongst them and they can be reset. Any fault in the
system will be presented as "General fault in system" and the
buzzer will sound.
FBP 1826. It will print all the alarms, including the alarm texts.
New S/W versions can be downloaded directly in the unit. The
unit is power supplied from EBL512 G3 or an ext. power
supply.
The unit shall run in S/W mode 1826/28 – 1587. Up to 1200 m
cable can be used.
description MEW00249.
1828 External Fire Brigade Panel (FBP). A compact size enclosure
(HxWxD, 145 x 220 x 50 mm) made of grey high impact ABS.
Fitted with a supplementary "O" ring gasket, it will comply
with IP61, in respect of dust and moisture. The unit has no
door, i.e. the front is accessed directly but a key is required to
45
Not valid for the Swedish convention (SBF).
45
A Printer 1835 can be mounted in ext.
For more information, see Technical
55
An