Activate Interlocking Output (H9/C2); Reset Interlocking Output (H9/C3); Disable Interlocking Output (H9/C4); Re-Enable Interlocking Output (H9/C5) - Panasonic MEW01 351 Planning Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01351
Rev: -
14.3.2
14.3.3
14.3.4
14.3.5
14.4
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
Use "↑" "↓" to scroll between several interlocking combinations.

Activate interlocking output (H9/C2)

Even if the control expression for an interlocking output is not
fulfilled (true), the output can be manually activated via this menu.
The "Interlocking Combination" (Area / Point) is to be entered to
activate the output. The corresponding interlocking input will be
"monitored" in the same way as if the output was activated by its
control expression.
Reset has to be performed via menu H9/C3.

Reset interlocking output (H9/C3)

Activated interlocking outputs are listed here. Use "↑" "↓" to scroll
between the "Interlocking Combinations" (Area / Point).
Interlocking output activated via its control expression and latched
output selected: The output has to be reset via this menu.
Interlocking output activated via its control expression and latched
output not selected: The output can be reset via this menu.
Interlocking output activated via menu H9/C2: The output has to be
reset via this menu.

Disable interlocking output (H9/C4)

Interlocking outputs (i.e. Output Type = Interlocking) can be
individually disabled via menu H9/C4. NOTE! Not via menu H2/B3.
A disabled output will stay in (or return to) the normal condition for
the output respectively. The "Interlocking Combination" (i.e. Area /
Point) is to be entered to disable the output.
Via menu H2/B7 can all interlocking outputs in the system be disabled
/ re-enabled.

Re-enable interlocking output (H9/C5)

Interlocking outputs (i.e. Output Type = Interlocking) can be re-
enabled via menu H9/C5. NOTE! Not via menu H2/B6.
Disabled interlocking outputs are listed in menu H9/C5. Use "↑" "↓"
to scroll between the "Interlocking Combinations" (i.e. Area / Point)
or type it via the key-pad.

Interlocking control expressions

A programmable output control expression can contain "interlocking"
trigger conditions ("Functions") numbers 15-18 (see chapter "Control
expression", page 76), i.e. one or more outputs can be activated when
one or more interlocking inputs are activated.
87