9.1.1.6
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
6295 Heat detector:
detector, 57°C, class A2 S (static response temp. range 54-
70°C), latching.
Min./typical/max. ambient temp. -40/+25/+50°C. Built-in LED
is lit to indicate that the detector has activated a fire alarm.
Terminals for an ext. LED (2218).
6296 Heat detector: Enclosed (IP67)
S (static response temp. range 69-85°C), latching.
Min./typical/max. ambient temp. -40/+40/+65°C. Built-in LED
is lit to indicate that the detector has activated a fire alarm.
Terminals for an ext. LED ( 2218).
6297 Heat detector: Enclosed (IP67). Like 6295 but 87°C, class C S
(static response temp. range 84-100°C), latching.
Min./typical/max. ambient temp. -40/+55/+80°C. Built-in LED
is lit to indicate that the detector has activated a fire alarm.
Terminals for an ext. LED (2218).
6298 Heat detector: Enclosed (IP67). Like 6295 but 117°C, class E S
(static response temp. range 114-130°C), latching.
Min./typical/max. ambient temp. -40/+85/+110°C. No built-in
LED but terminals for an ext. LED (2218) - to indicate that the
detector has activated a fire alarm.
Accessories
3314 Address setting tool. Is used to write or read the units' COM
loop address (Technical address 001-255). It is also used to
write or read the mode, see the unit respectively. In system
EBL512 G3 shall NORMAL mode always be used.
connection cable with crocodile clips and tab terminals is
supplied with the tool and can be used when required.
Put the ON/OFF switch in position ON and wait for a beep.
Plug the detector's SA & SB terminals onto the tool's SA & SB
terminals or, when required, use the connection cable.
How to read: Press "READ", wait for a beep and read the
address and mode.
How to write:
"READ" at the same time and/or write the address. Press
"WRITE" and wait for a beep. ("READ" again as a check.)
29
This detector holds the ATEX classification:
Ex II 3GD EEx nA II T5 (T 100°C), -40°C < T
30
This detector holds the ATEX classification:
Ex II 3GD EEx nA II T5 (T 100°C), -40°C < T
31
Some units have flying leads for easier connection. After use they should
be disconnected and thrown away.
29
Enclosed (IP67)
.
Fixed temperature heat
30
. Like 6295 but 72°C, class B
To select the mode, press "WRITE" and
< 50°C.
a
< 65°C.
a
45
A
31