Panasonic MEW01 351 Planning Manual page 84

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01351
Rev: -
13.5.3.3
13.5.3.4
13.5.3.5
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
NOT
Inverts a condition, e.g. NOT b = NOT 0=1.
a OR NOT b AND c = y
This is shown in the following table:
Parentheses
Changes priority order.
a OR NOT( b AND c ) = y
completed with parentheses.)
This is shown in the following table:
Control expressions
The AND operator has priority, i.e. a AND b OR c = (a AND b) OR c.
This is perhaps more obvious if you write it: a • b + c.
This means that: a AND b OR c ≠ a AND (b OR c).
a
b
c
y
0
0
0
0
0
0
1
1
0
1
0
0
0
1
1
0
1
0
0
1
1
0
1
1
1
1
0
1
1
1
1
1
(This is same as the previous but
a
b
c
y
0
0
0
1
0
0
1
1
0
1
0
1
0
1
1
0
1
0
0
1
1
0
1
1
1
1
0
1
1
1
1
1
82