Panasonic MEW01 351 Planning Manual page 49

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
address label on which the unit's COM loop address can be
written.
The Address setting tool (3314) is also used for the mode
setting:
NORMAL mode: Used for 3361 in system EBL512 G3.
2330 mode: Not used in system EBL512 G3.
2312 mode: Not used in system EBL512 G3.
3364
Addressable 2 voltage outputs unit. The unit is connected to
a COM loop. External 24 V DC power supply is required (via a
3366 unit or EBL512 G3).
The unit has two programmable and supervised voltage outputs
(VO0-VO1), intended for alarm devices (e.g. sirens). An end-
of-line capacitor (470nF) is to be mounted in the last device
alt. a capacitor (470nF) in up to five alarm devices:
The unit also has a special voltage output (VO2) intended for
fire door closing only.
closing" and the controlling detectors have to be programmed.
The "fire door closing function" is described on page 88 and
besides that function the output VO2 will also be powerless
approx. 30 sec. after:
- the "/Mains OK input" (terminal 8.) goes high, see below.
- the COM loop communication is interrupted = 3364 has no
connection / communication with EBL128.
The unit also has two inputs, i.e. one for power supply (24 V
DC) and one for "/Mains OK".
VO0:
Normally low or high (set via WinG3), 24 V DC,
36
1 A.
VO1: Like VO0.
VO2: Normally high, 24 V DC, 1 A.
function.)
24 V DC:
From an external power supply (unit 3366 or
EBL512 G3)
/Mains OK: From an external power supply unit (3366) when
the fire door closing function (ABDL) is to be used.
Normally low = The main power source
External power supply unit is okay.
Connections and examples, see drawings 512 G3 - 31 & - 38.
Unit dimensions: (L x W x H) 90 x 70 x 32 mm. A plastic
protection cover is attached. The cover dimensions: (L x W x
H) 129 x 73 x 45 mm. The unit is intended to be surface
mounted and for indoor use in dry premises. When required, the
unit can be mounted in a Waterproof box (IP66 / 67) 3362.
For more information, see the Technical Description and the
Product Leaflet.
The COM loop address is set with the Address setting tool
(3314). The unit has an address label on which the programmed
36
Cont. 1 A, during 10 ms 1.4 A.
The trigger condition "Fire door
36
(Fire door closing
47
(230 V AC) in the

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ebl512 g3

Table of Contents