Planning Instructions Fire alarm system EBL512 G3, V1.1.x
Logic
(•) Normally open / low Normally open relay contact or normally
65
low voltage output.
( ) Normally closed / high Normally closed relay contact or
normally high voltage output (24V DC).
Supervised / Not supervised
A voltage output is supervised (default).
"Supervised" checkbox the voltage output will be not supervised.
A normally high output cannot be supervised.
Output signal period
Each output uses an "Output signal period", which controls the
output's activation. The following are available:
User defined 1-8 can be built up with type and time.
Types:
0. Steady (continuous)
1. Intermittent
2. Pulse
3. Steady, Delayed Activation
4. Intermittent, Delayed Activation
5. Pulse, Delayed Activation
6. Steady, Delayed De-Activation
Times:
Delay time (when required)
Pulse length time (when required)
Pulse off time (when required)
De-activation time (when required)
65
The logic is set in the WinG3 dialog box "Voltage / Relayed Output".
66
The logic is set in the WinG3 dialog box "Voltage / Relayed Output".
NOTE! A normally high output can not be supervised and it will be low for
a few seconds during restart of the c.i.e.
66
73
By unmarking the