Planning Instructions Fire alarm system EBL512 G3, V1.1.x
Here follows some examples (and explanations) to show the principles
how to build a control expression with "conditions" and logical
operators.):
Example 1
Output:
Control expression:
Explanation:
Example 2
Output:
Control expression:
Explanation:
Example 3
Output:
Control expression:
Explanation:
Example 4
Output:
Control expression:
Explanation:
Voltage output S0
Pre Alarm Zone (90)
Pre-warning activated in zone no. 90 will
activate the output S0.
Relay output R1
General Control Off ( ) AND NOT Door
Open (01)
Controls OFF (via menu H2/B8) will
activate the output R1 when the door in
control unit 01 is not open (i.e. closed).
Relay output R0
Fire Alarm Zone (145) AND Fire Alarm
Zone (045) AND General Fault ( )
Fire alarm activated in zone 145 and zone 45
will activate the output R0 when there are
one ore more faults in the system at the same
time.
Voltage output S1
Consecutive Fire Alarm (100,10,100,19,1)
OR
Consecutive Fire Alarm (100,21,100,40,1)
Fire alarm activated by one of the alarm
points in zone 100 address 10-19 or
activated by one of the alarm points in zone
100 address 21-40 will activate the output
S1 (i.e. alarm point address 20 in zone 100
will not activate the output S1).
83