Panasonic MEW01 351 Planning Manual page 149

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Meter
900
850
800
750
700
650
600
550
500
450
400
350
300
250
200
150
100
0
40
Figure 31. Graphs showing the cable length in relation to the COM loop units' total
current consumption. NOTE! The graphs start at "0 mA" and 863 m cable length
respectively but graph 1 ends at "320 mA" and graph 2 ends at "350 mA". End of
graph = max. allowed loop current. (863 m cable length = 42.3 ohm.)
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
Maximum cable length
80
120
160
Total COM loop unit current consumption
NOTE! The graphs are valid for the cable type ELQYB 2 x 1 mm
2
(0.75mm
) with the conductor resistance 24.5 ohm / km. The total
conductor resistance (ohm) = L conductor (ohm) + C conductor
(ohm).
147
2 x 1 mm (0.75 mm
24.5 ohm / km
200
240
280
2
)
320
mA