Fan Control - Panasonic MEW01 351 Planning Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01351
Rev: -
6.5.2
6.5.3
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
Output no. (0-47)
Properties, like any programmable relay output.
Each input (0-15) has to be added and programmed via WinG3
regarding:
Input no. (0-15)
Type (of input)
Properties, like any programmable input.

Fan control

Used for Application board type Fan control, e.g. "Fan control
application board" 4594, which has a front for Fan control of up to
four fans.
Fan control panel 4593 has two Fan control application boards 4594
and two Fan control fronts (see page 52).
Each Fan (0-3) (i.e. each Fan control) has to be added and
programmed via WinG3.
For each fan (Fan control), also one I/O unit for fan control 3361
(COM loop unit) has to be added and programmed via WinG3
regarding e.g:
Technical address (COM loop address 1-255)
Name (Fan control I/O unit - normally not changed)
Fan control information
 I/O Matrix fan control (Fan control / fan 0-3)
 Supervised or not supervised (Input In0)
 Output latched or not latched
 Enhanced fan control function or not.
 Fault detection time (Input In0; 30-255 seconds)
Properties, like any programmable output.
Normally stopped or Normally running
Zone control
Used for Application board type Zone control.
Each input (0-15) has to be programmed via WinG3 regarding:
18
Zone control is normally used on the Australian market only.
18
33