Expansion Board No. (Address) Setting; Zones Expansion Board 4580 - Panasonic MEW01 351 Planning Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01351
Rev: -
6.1
Board no.
(address)
0
1
2
3
4
5
6.2
Planning Instructions Fire alarm system EBL512 G3, V1.1.x

Expansion board no. (address) setting

The expansion board no. (address) is set via jumpers on the expansion
board respectively.
4580, 4581 and 4583
JP2
JP3
Open
Open
Shunted
Open
Open
Shunted
Shunted
Shunted
Open
Open
Shunted
Open
Figure 5.
Expansion boards 4580 - 4583.
expansion board no. (address) setting.

8 zones expansion board 4580

Each board has to be programmed via WinG3 regarding:
Address / Board no. (set via the jumpers "JP2-JP4", see Figure 5
above.)
The 4580 board has eight conventional zone line inputs (0-7) intended
for conventional detectors. In the last alarm point on each zone line,
has to be connected an end-of-line device, depending on the selected
"Type of zone line input", see below.
Connections to "J1:1-16" and "J2" according to drawing 512 G3 - 33.
Each zone line input has to be programmed via WinG3 regarding:
Type of zone line input (see below), depending on detectors / end-
of-line device (capacitor or resistor), i.e. different threshold levels
etc.
Alarm at short circuit / No alarm at short circuit (i.e. if short-
circuit on the zone line shall generate a fire alarm or a fault)
Zone number (no address)
Fire alarm delay / No fire alarm delay
Text (Alarm text – if you wish)
Alert annunciation & time channel
Disablement & time channel
For more information, see the WinG3 help.
The terminals support a wire size up to 1.13 mm
JP4
JP1
Open
Open
Open
Shunted
Open
Open
Open
Shunted
Shunted
Open
Shunted
Shunted
2
27
4582
JP2
JP3
Open
Open
Open
Open
Shunted
Open
Shunted
Open
Open
Shunted
Open
Shunted
Jumpers for
(1.2 mm).