Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
In the dialog box for any alarm point (e.g. a detector/sensor)
is a "Text" field where the alarm text for that alarm point can be typed
(or edited). The alarm text will be shown in the c.i.e. display when
this alarm point has activated fire alarm.
Alarm text
Text editor
The alarm text can, as an alternative, be typed (or edited) in the
WinG3 "Text editor" (menu System | Edit Alarm Texts...).
No matter where the text is typed, it will be shown on both places.
Explanations:
Zone-Address column
Shows the already programmed alarm points (e.g. 001-01, 001-02,
002-01 etc.).
Only the texts have to be typed / edited in the "Text" column.
Shows the already programmed zones, i.e. I/O unit 3361 zone line
inputs programmed with address "00" (i.e. ZZZ – 00) and 8 zones
expansion board 4580 zone line inputs.
Only the texts have to be typed / edited in the "Text" column.
Text column
Shows already programmed alarm texts. Texts can be typed / edited
here.
109
In WinG3.
112
109
, there