Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
shall be used to read a true value instead of a calculated current
consumption.
A tip: Turn off the main power source (230 V AC) and use e.g. a
"clamp current meter" on one of the wires between one of the batteries
and the Main board 5010, to read the true total control unit current
consumption.
An approx. value is displayed via menu H5/A5.
157