Planning Instructions Fire alarm system EBL512 G3, V1.1.x

2-address (-unit) dependence

Each analog detector, addressable multi purpose I/O unit (3361)
monitored Input 0 (Z) and 8 zones expansion board (4580) input, can
be programmed for 2-unit dependent fire alarm activation. (Heat
detectors should not and manual call points must not be 2-unit
dependent).
Function:
Two or more units in the same zone have to be in "fire alarm state"
at the same time to activate a fire alarm in the control unit. When only
one unit is in "fire alarm state" it is indicated in the control unit (c.i.e.)
as follows:
The buzzer sounds like for pre-warning (0.8 / 5 sec.).
In the c.i.e. LCD the following information is shown:
Co-incidence alarm
Zone
ZZZ-AA
User definable alarm text.
Menu
Programmable outputs can be activated by trigger condition "Two
Address Dependent Fire Alarm" but no other outputs will be activated.
Reset of 2-zone / 2-address dependence (co-incidence
alarm
The unit / zone having activated a Co-incidence alarm will be latched
in this status for at least 5 minutes and then automatically reset.
During these 5 minutes the push button "Reset", on the c.i.e. front /
FBP, can be used to manually reset the Co-incidence alarm.
If, during these 5 minutes, at least one more unit (in the zone) or at
least one more zone (in the group) comes into "fire alarm state", the
Co-incidence alarm ends and normal fire alarms will be activated in
the c.i.e.