MEW01351
Rev: -
9.1.1.4
9.1.1.5
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
The Address setting tool (3314) is also used for mode setting:
NORMAL mode: 4301 in this mode is in WinG3 set to one of
the
six
algorithms
or N-35.
2330 mode: Not used in system EBL512 G3.
2312 mode: Not used in system EBL512 G3.
Conventional Detector Bases (CDB)
2324 Base. A conventional detector shall be plugged in 2324. Built-
in LED is lit to indicate that the detector plugged in the base has
activated fire alarm. Terminals for an ext. LED (2218).
Conventional Detectors
4318 Combination heat detector. Rate-of-rise and fixed temperature,
59°C, heat detector class A1 R. Static response temp. range 54-
65°C, ambient temp. min./typical/max. -10/+25/+50°C .
Shall be plugged in a conventional detector base (2324).
4350 Multi detector. 4350 is a smoke detector and a heat detector
within one housing. Scattered light (i.e. reflection of infrared
light) is used to detect smoke and the heat sensing element is a
thermistor. In order to secure the fire detection and to prevent
false (nuisance) alarms, an AI function is used, i.e.
a: combined heat and smoke sensing
b: variable delay function
c: adaptive learning function
See also chapter "Cyber sensor functions, page 121.
The detector has unleaded soldering.
Shall be plugged in a conventional detector base (2324).
4352 Photoelectric smoke detector. Scattered light (i.e. reflection of
infrared light) is used to detect smoke. An advanced alarm
algorithm is used to secure the smoke detection and to prevent
false (nuisance) alarms, e.g. a minimum of nine consecutive
readings over the fire alarm level are required before the
detector goes into alarm. (One reading per sec.)
The detector has unleaded soldering.
Shall be plugged in a conventional detector base (2324).
4375 Heat detector. Fixed temperature heat detector, 60°C, class
A2S (static response temp. range 54-70°C), latching.
Min./typical/max. ambient temp. -10/+25/+40°C.
The detector has unleaded soldering. Shall be plugged in a
conventional detector base (2324).
4376 Heat detector. Like 4375 but 80°C, class BS (static response
temp. range 69-85°C), latching.
Min./typical/max. ambient temp. -10/+40/+60°C.
The detector has unleaded soldering. Shall be plugged in a
conventional detector base (2324).
H-15,
H-35,
44
L-15,
L-35,
N-15