Panasonic EBL128 Planning Instructions page 39

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
Zone-Addr.
01-01 (smoke)
01-02 (heat)
Techn. addr.
123
Zone-Addr.
01-01 (smoke
or heat)
Techn. addr.
123
of three alarm algorithms (static response temp. range) for
class:
A1 (54-65°C), min./typical/max. ambient temp. -20/+25/+50°C
A2 S (54-70°C), min./typical/max. ambient temp. -20/+25/+50°C
B S (69-85°C), min./typical/max. ambient temp. -20/+40/+65°C
2330 mode: 3309 is in this mode like addressable heat detector
2340.
2312 mode: Not used in EBL128.
4300 Analog multi detector. Replaced with 4400, see below. A
smoke detector and a heat detector within one housing.
Scattered light (i.e. reflection of infrared light) is used to detect
smoke and the heat sensing element is a thermistor.
detector has unleaded soldering.
To be plugged in a base 3312xx/3379/4313. Built-in LEDs are
lit to indicate that the detector
Prepared for mechanical lock (screw attached).
Via EBLWin it is programmable how the detectors shall operate
(in NORMAL mode):
a)
Two presentation numbers (addresses): The detector
unit works as two separate detectors. The smoke detector is
programmed for one zone-address and the heat detector for
another zone-address
detectors during working hours and in control expressions for
programmable outputs). The detector unit has one technical
address set with Address setting tool 3314 / 4414, used for
programming and fault presentation. Another technical address
will automatically be occupied, i.e. 4300 occupies two
technical/COM loop addresses.
b)
One presentation number (address): The detector unit
works as one detector and is programmed for one zone-address.
The detector unit (actually the heat detector) can detect a
methylated spirits fire (EN54-9, test fire TF6; liquid fire), which
normally is impossible for a photo electric smoke detector to
detect. The detector unit has one technical address set with
Address setting tool 3314 / 4414, used for programming and
fault presentation. Another technical address will automatically
be occupied, i.e. 4300 occupies two technical/COM loop
addresses.
It is, via EBLWin, programmable if the detectors in alt. b) shall
work with "OR-functionality" or with a "Decision algorithm":
36
I.e. the heat detector and/or the smoke detektor.
37
The zone number has to be the same for both detectors. NOTE! When
counting alarm points these "two detectors" are regarded as two alarm points.
EBL128 Planning Instructions V2.0.x
36
has generated fire alarm.
37
. (Can be used to disable one of the
37
The