Panasonic EBL128 Planning Instructions page 38

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
6.1.1.3
type of front cover and backbox. For surface mounting. For
indoor use in premises where IP67 rating is required.
The Address setting tool is also used for mode setting.
NORMAL mode: Flashing or not flashing LED (see Product
leaflet MEW00098) is set via EBLWin.
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
4439 Enclosed Addressable Manual Call Point with isolator.
Replaces 3339, see above. 4439 is like 3339 but it also has a
built-in short circuit isolator. (The function is described at page
49.) The isolator does not use any COM loop address.
The Address setting tool is also used for mode setting.
NORMAL mode: The built-in short circuit isolator is in use.
Flashing or non-flashing LED is set via EBLWin.
2330 mode: The built-in short circuit isolator is not in use.
4439 replaces a 3339 mcp. Flashing or non-flashing LED is set
via EBLWin.
2312 mode: The built-in short circuit isolator is not in use.
4433 replaces a 2339 mcp. Flashing LED.
Analog Detectors
3308 Analog heat detector.
3312xx/3379/4313. Built-in LED that is lit to indicate that the
detector has generated fire alarm. Prepared for mechanical lock
(screw attached). The technical address is set with Address
setting tool 3314 / 4414. The detector has an address label on
which the programmed technical address is to be written.
The Address setting tool is also used for mode setting:
NORMAL mode: 3308 is in this mode via EBLWin set to one
of three alarm algorithms (static response temp. range) for
class:
A1 (54-65°C), min./typical/max. ambient temp. -20/+25/+50°C
A2 S (54-70°C), min./typical/max. ambient temp. -20/+25/+50°C
B S (69-85°C), min./typical/max. ambient temp. -20/+40/+65°C
2330 mode: 3308 is in this mode (+ base 3312) works like the
conventional heat detector 6270/6275 (+ base 2330).
2312 mode: Not used in EBL128.
3309 Analog heat detector. Enclosed (IP67)
lit to indicate that the detector has generated fire alarm.
Terminals for ext. LED 2217 /2218. Recess for label holder
3391. The technical address is set with Address setting tool
3314 / 4414, which is also used for mode setting:
NORMAL mode: 3309 is in this mode via EBLWin set to one
35
As from July 2013, this detector holds the ATEX classification:
Ex II 3 G Ex ic IIC T5 Gc, Ex II 3 D Ex ic IIIC T70°C Dc,
-20°C < T
< 65°C.
a
EBL128 Planning Instructions V2.0.x
To be plugged in a
35
. Built-in LED that is