Name
76.13
Pump/fan status 3
76.14
Pump/fan status 4
76.21
PFC configuration
76.25
Number of motors
76.26
Min number of motors allowed
76.27
Max number of motors al-
lowed
76.30
Start point 1
76.31
Start point 2
76.32
Start point 3
76.41
Stop point 1
76.42
Stop point 2
76.43
Stop point 3
76.55
Start delay
76.56
Stop delay
76.57
PFC speed hold on
76.58
PFC speed hold off
76.59
PFC contactor delay
76.60
PFC ramp acceleration time
76.61
PFC ramp deceleration time
76.70
PFC autochange
Not selected[0]
Selected[1]
DI1[2]
76.71
PFC autochange interval
76.72
Maximum wear imbalance
Range/List
See parameter 76.11
Pump/fan status 1
See parameter 76.11
Pump/fan status 1
Off[0], PFC[2], SPFC[3]
1...4
0...4
1...4
0...32767
0...32767
0...32767
0...32767
0...32767
0...32767
0.00...12600.00
0.00...12600.00
0.00...1000.00
0.00...1000.00
0.20...600.00
0.00...1800.00
0.00...1800.00
0...13
DI2[3]
DI5[6]
DI3[4]
DI6[7]
DI4[5]
Timed function
1[8]
0.00...42949672.95
0.00...1000000.00
Parameter listing 109
Unit
Default
-
0b0000
-
0b0000
-
Off[0]
-
1
-
1
-
1
Hz
48
Hz
48
Hz
48
Hz
25
Hz
25
Hz
25
s
10.00
s
10.00
s
0.00
s
0.00
s
0.50
s
1.00
s
1.00
-
Not selected[0]
Timed function
All stop[12]
2[9]
Timed function
Even wear[13]
3[10]
Fixed inter-
Other...
val[11]
h
1.00
h
10.00
EN
HI