158 HI -त् व रित इं स ् ट ाले श न और स् ट ार् ट -अप गाइड
Measuring the insulation of the motor and motor cable
Obey the safety instructions of the drive. If you ignore them, injury or death, or
damage to the equipment can occur.
If you are not a qualified electrical professional, do not do installation or
maintenance work.
1. Do the steps in section Electrical safety precautions before you start the work.
2. Make sure that the motor cable is disconnected from the drive output terminals.
3. Measure the insulation resistance between each phase conductor and the protective
earth conductor. Use a measuring voltage of 1000 V DC. The insulation resistance
of an ABB motor must be more than 100 Mohm (reference value at 25 °C [77 °F]).
For the insulation resistance of other motors, refer to the manufacturer's instructions.
EN
टिप् प णी
[ Translation missing]
the insulation resistance. If you think that there is moisture in the motor, dry the
HI
motor and do the measurement again.
1000 V DC,
> 100 Mohm
ohm
Moisture inside the motor casing reduces
U1
U1-PE, V1-PE, W1-PE
M
V1
3~
W1
PE