Auto configuration of I/O's and fieldbus module
You can configure the connected optional modules or/and fieldbus modules automatically.
1. Switch off the drive and connect the required modules. For more information on
optional modules and its installation, see chapter Electrical installation in the
hardware manual.
2. Switch on the drive and set parameter 07.35 Drive configuration bit list values to 0.
3. Restart the drive.
The drive configures the connected modules, its respective parameters and the
fieldbus settings.
For example, to auto configure the BIO-01 module and/or FPBA fieldbus modules, set
parameter 07.35 Drive configuration bit list values to 0 and restart the drive. The drive
configures the following parameters automatically:
sets parameter 07.35 Drive configuration bits 5 (FPBA-01) and 8(BIO-01) to ON,
enables BIO-01 related parameters, and