Siemens SIMATIC Manual page 163

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Dimensions and weight
Voltages, currents, electrical potentials
Rated electronics supply voltage L +
Reverse polarity protection
Power failure buffering
Total current of outputs (per group)
horizontal mounting position
up to 60 °C
other mounting positions
to 40 °C
Cumulated current of outputs (per module)
horizontal mounting position
to 60 °C
other mounting positions
to 40 °C
Electrical isolation
between channels and the backplane bus
between channels and electronics power supply
between channels
in groups of
Maximum potential difference
between channels and the backplane bus
between channels and electronics power supply
between outputs of different groups
Isolation test voltage
between channels and the backplane bus
between channels and electronics power supply
between outputs of different groups
Current consumption
from the backplane bus
from supply voltage L+
Power loss of the module
Status, interrupts, diagnostics
Status display
Diagnostic functions
Group error display
Interrupts
Diagnostic interrupt
Reading diagnostics information
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
3.26 Digital output module SM 322; DO 16 x UC 24/48 V; (6ES7322-5GH00-0AB0)
24 V DC
yes
min. 5 ms
max. 0.5 A
max. 0.5 A
max. 8 A
max. 8 A
yes
yes
yes
1
170 V DC, 120 V AC
170 V DC, 120 V AC
170 V DC, 120 V AC
1500 V AC
1500 V AC
1500 V AC
max. 100 mA
max. 200 mA
typ. 2.8 W
green LED per channel
red LED (SF)
programmable
supported
Digital modules
163

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-300S7-300 module data

Table of Contents