Dimensions and weight
Voltages, currents, electrical potentials
Rated electronics supply voltage L +
•
Reverse polarity protection
•
Power failure buffering
Total current of outputs (per group)
•
horizontal mounting position
up to 60 °C
•
other mounting positions
to 40 °C
Cumulated current of outputs (per module)
•
horizontal mounting position
to 60 °C
•
other mounting positions
to 40 °C
Electrical isolation
•
between channels and the backplane bus
•
between channels and electronics power supply
•
between channels
in groups of
Maximum potential difference
•
between channels and the backplane bus
•
between channels and electronics power supply
•
between outputs of different groups
Isolation test voltage
•
between channels and the backplane bus
•
between channels and electronics power supply
•
between outputs of different groups
Current consumption
•
from the backplane bus
•
from supply voltage L+
Power loss of the module
Status, interrupts, diagnostics
Status display
Diagnostic functions
•
Group error display
Interrupts
•
Diagnostic interrupt
•
Reading diagnostics information
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
3.26 Digital output module SM 322; DO 16 x UC 24/48 V; (6ES7322-5GH00-0AB0)
24 V DC
yes
min. 5 ms
max. 0.5 A
max. 0.5 A
max. 8 A
max. 8 A
yes
yes
yes
1
170 V DC, 120 V AC
170 V DC, 120 V AC
170 V DC, 120 V AC
1500 V AC
1500 V AC
1500 V AC
max. 100 mA
max. 200 mA
typ. 2.8 W
green LED per channel
red LED (SF)
programmable
supported
Digital modules
163