Siemens SIMATIC Manual page 53

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Table 3- 5
Digital output modules (continued)
Properties
Number of outputs
Output current
Rated load voltage
Suitable for...
Supports isochronous
mode
Programmable
diagnostics
Diagnostic interrupt
Substitute value output
Special features
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
SM 322; DO 16 x
SM 322; DO 16 x
DC24V/0,5A High
UC24/48 V
Speed
(-1BH10-)
(-5GH00-)
16 DO; isolated in
16 DO; isolated in
groups of 8
groups of 1
0.5 A
0.5 A
24 V DC
24 to 48 V DC
24 to 48 V AC
solenoid valves, DC contactors and signal lamps
Yes
no
No
Yes
no
Yes
Fast module;
-
especially for
isochronous
mode
Module
SM 322; DO 16 x
SM 322; DO 16 x
AC120/230V/1A
DC24V/0,5A
(-8BH00-)*
(-1FH00-)
(-8BH01-) *
(-8BH10-)
16 DO; isolated in
16 DO; isolated in
groups of 8
groups of 4
1 A
0.5 A
120/230 V AC
24 V DC
no
no
no
yes
No
Yes
Yes
-
Redundant load
control is sup-
ported; extensive
control functions
Digital modules
3.1 Module overview
SM 322; DO 8 x
DC24V/2A
(-1BF01-)
8 DO; isolated in
groups of 4
2 A
24 V DC
no
no
No
No
-
53