Technical specifications
Destruction limit against external voltages/currents
•
Voltage at outputs to M
•
Current
•
Wiring of the actuators
•
for voltage output
–
2-wire connection
–
4-wire connection (measuring line)
•
for current output
–
2-wire connection
Reassigning parameters in RUN
If you reassign parameters in RUN, the following special characteristic applies.
SF LED is lit:
If a diagnostics was pending prior to reconfiguration, the SF LEDs (on CPU, IM or module)
may be lit even though diagnostics is no longer pending and the module is operating
correctly.
Solution:
● Only assign new parameters if no diagnostics is pending, or
● unplug module and plug it in again.
6.15.1
Output ranges of SM 332; AO 2 x 12 Bit
Introduction
You can configure the outputs for operation as voltage or current outputs, or disable them.
You program the outputs at the "output type" parameter in
Output type "Voltage" and output range "± 10 V" are set by default at the module. You can
always use this combination of output type and range without having to program the SM 332;
AO 2 x 12 Bit in
Output ranges
Program the voltage and current output ranges in
Table 6- 38
Selected type of output
Voltage
Current
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
6.15 Analog output module SM 332; AO 2 x 12 Bit; (6ES7332-5HB01-0AB0)
ANA
STEP 7
.
Output ranges of SM 332; AO 2 x 12 Bit
max. 18 V continuous;
75 V for the duration of max. 1 s (duty factor 1:20)
max. 50 mA DC
using a 20-pin front connector
supported
supported
supported
STEP 7
.
STEP 7
.
Output range
1 V to 5 V
0 V to 10 V
± 10 V
0 mA to 20 mA
4 mA to 20 mA
± 20 mA
Analog modules