Measuring Ranges - Siemens SIMATIC Manual

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Table A- 23
Measuring ranges codes of the analog input module
Measurement type
disabled
Voltage
Current
Resistance
Thermoelectric resistance
(linear)
Temperature coefficient
The table below lists the temperature coefficient codes to be entered at bytes 10 to 13 of
data record 1 (refer to previous figure.)
Table A- 24
Temperature measurement codes of the analog input module
Temperature coefficient
Pt 0.003850 Ω/Ω/°C (ITS-90)
Ni 0.006180 Ω/Ω/°C
Ni 0.005000 Ω/Ω/°C
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
Code
Measuring range
2#0000
disabled
2#0001
± 50 mV
± 500 mV
± 1 V
± 5 V
1 V to 5 V
0 V to 10 V
± 10 V
2#0010
0 mA to 20 mA
4 mA to 20 mA
± 20 mA
600 Ω
2#0101
6 kΩ
PTC
2#1001
Pt 100 Klima
Pt 100 Standard
Ni 100 Klima
Ni 100 Standard
Ni 1000 / LG-Ni 1000 Klima
Ni 1000 / LG-Ni 1000 Standard
KTY83/110
KTY84/130
A.9 Parameters of analog input module SM 331; AI 8 x 13 Bit
Measuring range
Pt 100
Ni 100 / Ni 1000
LG-Ni 1000
Parameter sets of signal modules
Code
2#0000
2#1011
2#0011
2#0100
2# 0110
2#0111
2#1000
2#1001
2#0010
2#0011
2#0100
2#0110
2#1000
2#1111
2#0000
2#0010
2#0001
2#0011
2#1010
2#0110
2#1100
2#1101
Code
2#0100
2#1000
2#1010
559

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-300S7-300 module data

Table of Contents