Digital modules
3.32 Digital output module SM 322; DO 8 x AC 120/230 V/2 A ISOL (6ES7322-5FF00-0AB0)
Technical specifications
Status, interrupts, diagnostics
Status display
Interrupts
•
Diagnostic interrupt
Diagnostic functions
•
Group error display
Actuator selection data
Output voltage
•
"1" signal
–
At maximum current
–
At minimum current
Output current
•
"1" signal
Rated value
permissible range at 0 °C to 40 °C
permissible range at 40 °C to 60 °C
Maximum inrush current (per group)
•
"0" signal (residual current)
Zero transition
Size of the motor starter
Lamp load
Wiring two outputs in parallel
•
for redundant load control
•
for performance increase
Control of a digital input
Switching frequency
•
with resistive load
•
with inductive load to IEC 947-5-1, AC 15
•
with lamp load
Short circuit-proof output
Wiring of the actuators
Note
The outputs must be protected by a high-speed, fast-blow 3.15 A 250 V AC fuse. Hazardous
areas to National Electric Code must be determined safe before you remove/replace the
fuse. Removal and replacement may only be possible using a suitable tool.
194
green LED per channel
programmable
red LED (SF)
min. L1 (-1.5 V)
min L1 (-8.5 V)
2 A
10 mA to 2 A
10 mA to 1 A
20 A (with two half-waves)
max. 2 mA
max. 60 V
max. size 5 to NEMA
max. 50 W
supported
not supported
supported
max. 10 Hz
max. 0.5 Hz
max. 1 Hz
yes, 3.15 A / 250 V fuse, fast-blow
Using a 40-pin front connector
Manual, 06/2017, A5E00105505-AJ
S7-300 Module data