Siemens SIMATIC Manual page 264

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Principles of analog modules
5.1 Representation of the values for analog input channels
Table 5- 6
Representation of analog values in the ±80 mV to ±500 mV voltage measuring ranges
System
Voltage measuring range
dec
hex
±500 mV
32767
7FFF
592.6 mV
32512
7F00
32511
7EFF
587.9 mV
27649
6C01
27648
6C00
500 mV
20736
5100
375 mV
1
1
18.08 µV
0
0
0 mV
-1
FFFF
-20736
AF00
-375 mV
-27648
9400
-500 mV
-27649
93FF
-32512
8100
-587.9 mV
-32513
80FF
-32768
8000
-592.6 mV
Table 5- 7
Representation of analog values in the 1 V to 5 V and 0 V to 10 V voltage measuring ranges
System
Voltage measuring range
dec
hex
1 V to 5 V
32767
7FFF
5.741 V
32512
7F00
32511
7EFF
5.704 V
27649
6C01
27648
6C00
5 V
20736
5100
4 V
1
1
1 V + 144.7 µV
0
0
1 V
-1
FFFF
-4864
ED00
0.296 V
-4865
ECFF
-32768
8000
264
±250 mV
±80 mV
296.3 mV
94.8 mV
294.0 mV
94.1 mV
250 mV
80 mV
187.5 mV
60 mV
9.04 µV
2.89 µV
0 mV
0 mV
-187.5 mV
-60 mV
-250 mV
-80 mV
-294.0 mV
-94.1 mV
-296.3 mV
-94.8 mV
0 V to 10 V
11.852 V
11.759 V
10 V
7.5 V
0 V + 361.7 µV
0 V
Negative values are not sup-
ported
Overflow
Overshoot range
Rated range
Undershoot range
Underflow
Overflow
Overshoot range
Rated range
Undershoot range
Underflow
Manual, 06/2017, A5E00105505-AJ
S7-300 Module data

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-300S7-300 module data

Table of Contents